Based on the 2023 NEC.
Question: An additional service is permitted when the capacity requirements exceed ___________ amps at a supply voltage of 1,000V or less.
See answer below.
Answer: 2,000
Explanation: The answer to this question is found in Sec. 230.2(C)(1). That section permits an additional service "Where the capacity requirements are in excess of 2,000A at a supply voltage of 1,000V or less."
Lupacchino is a senior design engineer with Gaylor Electric, Inc. in Noblesville, Ind. and serves as an alternate on NEC Code-Making Panel No. 3. He is currently licensed in more than 80 jurisdictions. He can be reached at [email protected]