Code Q&A: NEC Requirements for Branch-Circuit Conductor Ampacity
Feb. 8, 2024
Courtesy of www.MikeHolt.com. Based on the 2023 NEC.
Question: Branch-circuit conductors supplying a single continuous-duty motor shall have an ampacity not less than _____ rating.
a) 125% of the motor’s nameplate current
b) 125% of the motor’s full-load current
c) 125% of the motor’s full locked-rotor
d) 80% of the motor’s full-load current
See answer below.
Answer: b) 125% of the motor’s full-load current
According to Sec. 430.22, "Condusctors that supply a single motor used in a continuous duty application shall have an ampacity of not less than 125% of the motor’s full-load current rating."
These materials are provided by Mike Holt Enterprises in Leesburg, Fla. To view Code training materials offered by this company, visit www.mikeholt.com/code.
Sponsored Recommendations
Sponsored Recommendations
Sponsored
Sponsored