Based on the 2023 NEC.
Question: True or false? A receptacle located within 6 ft of the top of an aquarium located in an office building requires GFCI protection.
See answer below.
Answer: True
Explanation: Section 210.8(B)(13) was added to the 2023 NEC to require GFCI protection for receptacles located within 6 ft of the top inside edge of aquariums, bait wells, and similar open aquatic vessels or containers such as tanks or bowls.
Lupacchino is a senior design engineer with Gaylor Electric, Inc. in Noblesville, Ind. and serves as an alternate on NEC Code-Making Panel No. 3. He is currently licensed in more than 80 jurisdictions. He can be reached at [email protected]