Code Quiz: Minimum Number of Receptacles at a Patient Bed Location
Based on the 2020 NEC.
Question: What is the minimum number of receptacles required at a patient bed location in a Category 1 (Critical Care) space?
See answer below.
Answer: 14
Explanation: This minimum receptacle requirement is outlined in Sec. 517.19(B)(1) of the 2020 NEC. One of these receptacles shall be connected to the normal system branch circuit required by Sec. 517.19(A) or a critical branch circuit supplied by a different transfer switch than the other receptacles at the same patient bed location.