Code Quiz: Minimum Number of Receptacles at a Patient Bed Location

March 16, 2022
Test your knowledge of the NEC with this challenging question.

Based on the 2020 NEC.

Question: What is the minimum number of receptacles required at a patient bed location in a Category 1 (Critical Care) space?

See answer below.

Answer: 14

Explanation: This minimum receptacle requirement is outlined in Sec. 517.19(B)(1) of the 2020 NEC. One of these receptacles shall be connected to the normal system branch circuit required by Sec. 517.19(A) or a critical branch circuit supplied by a different transfer switch than the other receptacles at the same patient bed location.

Lupacchino is a senior design engineer with Gaylor Electric, Inc. in Noblesville, Ind. and serves as an alternate on NEC Code-Making Panel No. 3. He is currently licensed in more than 80 jurisdictions. He can be reached at [email protected].

About the Author

John Lupacchino | Senior Design Engineer

John began his career in electrical construction as an apprentice and worked his way through the trade. He is currently licensed in more than 80 jurisdictions. With more than 35 years of experience, he now plays a vital role in Gaylor Electric’s Engineering Department, where he serves as a senior design engineer. With a focus on design engineering, quality assurance, and code compliance, he has earned the highest level of respect from industry professionals alike. John currently serves as an alternate on NFPA 70 Code Making Panel No. 3. In addition, he enjoys sharing his electrical knowledge through education. As an Associated Builders and Contractors instructor, he continues to help grow a new generation of high-performing construction leaders.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Sponsored