Q. What are the NEC branch circuit requirements for storage water heaters?
See the answer below.
A. An electric water heater having a capacity of 120 gallons or less is considered a continuous load for the purpose of sizing branch circuits [Sec. 422.13].
Branch-circuit conductors must have a rating of at least 125% of the ampere rating of a continuous load [Sec. 422.10] and the overcurrent protection is sized in accordance with Sec. 422.11(E)(3).