Q. What is the NEC rule for the installation of bushings on rigid metal conduit (RMC)?
See the answer below.
A. To protect conductors from abrasion, a metal or plastic bushing must be installed on conduit threads at terminations, regardless of conductor size, unless the box, fitting, or enclosure is designed to provide this protection [Sec. 344.46].
Informational Note: Conductors 4 AWG and larger that enter an enclosure must be protected from abrasion, during and after installation, by a fitting that provides a smooth, rounded, insulating surface, such as an insulating bushing, unless the design of the box, fitting, or enclosure provides equivalent protection, in accordance with Sec. 300.4(G).