While it’s true the requirements for temporary wiring in the National Electrical Code (NEC) [Art. 590] are “relaxed” compared to those of permanent wiring, it’s not true that temporary means “slap it up” in any convenient manner. For example, if it involves a service (bringing power to the site) you must apply the requirements in Art. 230.
Here are some highlights from this part of the NEC:
- Since we don’t run temporary cables and cords in raceway, you must provide adequate support [Sec. 590.4(J)] and protection [Sec. 590.4(H). For example, route them out of the way of foot traffic, avoiding sharp edges.
- If you use lamps, they must be protected from accidental contact or breakage by a suitable luminaire or lampholder with a guard [Sec. 590.4(F)].
- You must protect personnel with GFCIs [Sec. 590.6]. But test them during and after installation. The protection provided by GFCIs is often bypassed due to incorrect wiring. Use a meter to verify the supply wires are, indeed, the supply wires and the wires connected on the load side are not supply wires.
Sponsored Recommendations
Sponsored Recommendations
Sponsored
Sponsored