Based on the 2020 NEC.
Question: True or False? Service entrance conductors entering a building are limited to 10 ft in length before connecting to the service disconnect.
See answer below.
Answer: False
Explanation: Section 230.70(A)(1) of the 2020 NEC requires the service disconnect to be located "nearest the point of entrance of the service conductors." No maximum length is specified. Since nearest the point of entry can be subject to the interpretation of the AHJ some jurisdictions will specify the length of conductor permitted and 10 ft is a common interpretation for many AHJs.
Lupacchino is a senior design engineer with Gaylor Electric, Inc. in Noblesville, Ind. and serves as an alternate on NEC Code-Making Panel No. 3. He is currently licensed in more than 80 jurisdictions. He can be reached at [email protected].