Q. Please explain the 25-ft tap rules in the NEC?
Find the Answer
A. Feeder tap conductors up to 25 ft long are permitted without overcurrent protection at the tap location if the tap conductors comply with the following [240.21(B)(2)] (see Figure):
• The ampacity of the tap conductors must not be less than one-third the rating of the overcurrent device that protects the feeder [240.21(B)(2)(1)].
• The tap conductors terminate in an overcurrent device rated no more than the tap conductor ampacity in accordance with 310.15 [240.21(B)(2)(2)].