Code Q&A: Bonding Aboveground Pools

Oct. 4, 2012
Your most pressing National Electrical Code (NEC) questions answered

Q. Do the equipotential bonding requirements of Part II of Art. 680 apply to storable swimming pools?

A. No. Electrical installations for storable pools must comply with Part I of Art. 680 [see 680.30]. They are not required to follow the equipotential bonding requirements of Part II. The requirements contained in Part I of Art. 680 include the locations of switches, receptacles, and luminaires.

A storable swimming pool is defined in 680.2 as an aboveground pool with a maximum water depth of 42 in. Storable pools are sold as a complete package that consists of the pool walls, vinyl liner, plumbing kit, and pump/filter device. Underwriters Laboratories, Inc. (UL) requires the pump/filter units to have a minimum 25-ft cord to discourage the use of extension cords.

About the Author

Mike Holt

Mike Holt is the owner of Mike Holt Enterprises (www.MikeHolt.com), one of the largest electrical publishers in the United States. He earned a master's degree in the Business Administration Program (MBA) from the University of Miami. He earned his reputation as a National Electrical Code (NEC) expert by working his way up through the electrical trade. Formally a construction editor for two different trade publications, Mike started his career as an apprentice electrician and eventually became a master electrician, an electrical inspector, a contractor, and an educator. Mike has taught more than 1,000 classes on 30 different electrical-related subjects — ranging from alarm installations to exam preparation and voltage drop calculations. He continues to produce seminars, videos, books, and online training for the trade as well as contribute monthly Code content to EC&M magazine.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Sponsored