In health care facilities, receptacles with insulated grounding terminals, as described in 250.146(D) shall be permitted in patient care areas.
a) True
b) False
See answer and applicable Code reference
The correct answer is: b) False
As noted in the scope of Art. 517, "the provisions of this article shall apply to electrical construction and installation criteria in health care facilities that provide services to human beings." The wiring and protection requirements for these areas are outlined in Part II of this article. As noted in Sec. 517.16, "receptacles with insulated grounding terminals, as described in 250.146(D), shall not be permitted."