Code Quiz

What is the minimum cubic inch area required for a terminal housing supplied with a generator?

Q. What is the minimum cubic inch area required for a terminal housing supplied with a generator? The conductors installed within the terminal housing are as follows: four No. 6 AWG THHW branch-circuit conductors and four No. 8 AWG MTW insulated conductors.

  1. This calculation does not apply to a terminal housing supplied with the generator.
  2. 20 cubic inches minimum. This applies only to the branch circuit conductors.
  3. 12 cubic inches minimum
  4. 32 cubic inches minimum

Answer: A

The 2008 NEC added generators as one of two items that do not have to comply with the requirements set forth in 314.16 when the terminal housing is supplied with the generator. The other item that does not have to comply with 314.16 is the motor terminal housing supplied with the motor.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at necexpert@aol.com.

Discuss this Article 0

Post new comment
Sign In or register to use your Electrical Construction & Maintenance (EC&M) Magazine ID
(optional)

White Papers
EC&M Learning Center
Webinars
EC&M TV
Apr. 15, 2013
video

The Westex Difference

Learn what sets Westex apart from other flame resistant fabric manufacturers....More

Newsletter Signup

Connect With Us