On a 3-phase, 4-wire, 480/277V service, a question has arisen as to the required rating of the service disconnect. The calculated load is 780A. The fusible disconnecting means is rated at 1,000A, based on the maximum fuse size that can be installed.

Q. On a 3-phase, 4-wire, 480/277V service, a question has arisen as to the required rating of the service disconnect. The calculated load is 780A. The fusible disconnecting means is rated at 1,000A, based on the maximum fuse size that can be installed. What is the minimum rating of the service disconnect permitted for this application?

  1. 800A
  2. 900A
  3. 1,000A
  4. All of the above

Answer: C

As per the second paragraph of 230.95, “The rating of the service disconnect shall be considered to be the rating of the largest fuse that can be installed or the highest continuous current trip setting for which the actual overcurrent device installed in a circuit breaker is rated or can be adjusted.”

The calculated value in this example would have permitted an 800A rated disconnecting means, however, because of the possibility of a 1,000A rated fuse being installed in this disconnect, the rating of this disconnect shall be a minimum of 1,000A.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Strut Comparison Chart

Conduit support systems are an integral part of construction infrastructure. Compare steel, aluminum and fiberglass strut support systems.

Electrical Conduit for Bridges Guide

Learn about electrical conduit for bridge projects.

Don't Let Corrosion Disrupt Your Next Project

The Complete Corrosion eGuide for Industrial Electrical Systems will help you avoid corrosion and its effects so you can spec for success for successful project outcomes.

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...