Code Quiz

March 3, 2011
Per 250.190(B), when grounding a 5kV rated service disconnect operating at 4.16kV, what is the minimum size grounding electrode conductor for this service to connect the non-current metal parts of the metal-clad enclosure to ground?

Per 250.190(B), when grounding a 5kV rated service disconnect operating at 4.16kV, what is the minimum size grounding electrode conductor for this service to connect the non-current metal parts of the metal-clad enclosure to ground? Assume the largest service-entrance phase conductor is 350kcmil and the equipment involved is fixed equipment.

  1. 350kcmil aluminum
  2. 3/0 AWG copper
  3. 1/0 AWG copper
  4. 2 AWG copper

Answer: D

Per this new section of the Code, the minimum size of the grounding electrode conductor is based on the size of the largest ungrounded phase conductor. A quick check of Table 250.66 reveals that a 350kcmil copper phase conductor requires a minimum size 2 AWG copper grounding electrode conductor.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Strut Comparison Chart

Conduit support systems are an integral part of construction infrastructure. Compare steel, aluminum and fiberglass strut support systems.

Electrical Conduit for Bridges Guide

Learn about electrical conduit for bridge projects.

Don't Let Corrosion Disrupt Your Next Project

The Complete Corrosion eGuide for Industrial Electrical Systems will help you avoid corrosion and its effects so you can spec for success for successful project outcomes.

Strut Corrosion Guide

Learn how Champion Strut™ benefits projects with corrosion resistance.