Code Q&A: Neutral Conductor

Your most pressing National Electrical Code (NEC) questions answered

Q. Is a neutral conductor allowed to be switched for 3-way or 4-way switching?

A. Wiring for 3-way and 4-way switching must be done so that only the ungrounded conductors are switched [404.2(A), as shown in the Figure below. In other words, the neutral conductor must not be switched. The white insulated conductor within a cable assembly can be used for single-pole, 3-way, or 4-way switch loops if it's permanently re-identified to indicate its use as an ungrounded conductor at each location where the conductor is visible and accessible [200.7(C)(2)].

If a metal raceway or metal-clad cable contains the ungrounded conductors for switches, the wiring must be arranged to avoid heating the surrounding metal by induction. This is accomplished by installing all circuit conductors in the same raceway in accordance with 300.3(B) and 300.20(A), or ensuring that they're all within the same cable.

Discuss this Article 5

rltomkinson
on Aug 9, 2012

Now that a neutral wire is required at switches, can you still use it as a traveler?

Jose A. Guillen (not verified)
on Aug 9, 2012

As long as the neutral conductor is identified with red or black tape i think we are ok to use it as a traveler

Anonymous (not verified)
on Aug 10, 2012

good point about neut req'd at switch. This drawing appears to contain a code violation (?)

Anonymous (not verified)
on Oct 22, 2012

that drawing shows a white wire not a neutral.

Anonymous (not verified)
on Nov 5, 2012

is there a distance req. for a100 amp breaker panel from a door or window.

Post new comment
Sign In or register to use your Electrical Construction & Maintenance (EC&M) Magazine ID
(optional)

White Papers
EC&M Learning Center
Webinars
EC&M TV
Apr. 15, 2013
video

Westex Flash Fire Testing Overview

See side-by-side comparisons of different flame resistant fabrics exposed to flash fires, illustrating the extent, severity and location of burns....More

Newsletter Signup

Connect With Us