Code Q&A: Bonding Metallic and Nonmetallic Water Piping Systems

Feb. 16, 2012
Your most pressing National Electrical Code (NEC) questions answered

Q. Are you required to bond isolated sections of metal water pipe that are connected to a nonmetallic water piping system?
 

A. No. An isolated section of metal pipe is not a metal water piping system. A metal water piping system must be bonded as required in 250.104(A)(1), (A)(2), or (A)(3). The bonding jumper must be copper where it is within 18 in. of the earth [250.64(A)], securely fastened to the surface on which it's mounted [250.64(B)], and adequately protected if exposed to physical damage [250.64(B)]. In addition, all points of attachment must be accessible [250.104(A)]. In addition, you're not required to bond isolated sections of metal water piping connected to a nonmetallic water piping system (Figure).

To remove dangerous voltage on metal parts from a ground fault, electrically conductive metal water piping systems, metal sprinkler piping, metal gas piping, as well as exposed structural steel members likely to become energized, must be connected to an effective ground-fault current path [250.4(A)(4)].

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Strut Comparison Chart

Conduit support systems are an integral part of construction infrastructure. Compare steel, aluminum and fiberglass strut support systems.

Electrical Conduit for Bridges Guide

Learn about electrical conduit for bridge projects.

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...