Based on the 2023 NEC.
Question: A single electrode consisting of a rod, pipe, or plate electrode shall have a resistance to ground of ________________ ohms or less.
See answer below.
Answer: 25
Explanation: According to Sec. 250.53 (A) (2) Ex., "If a single rod, pipe, or plate grounding electrode has a resistance to earth of 25 ohms or less, the supplemental electrode shall not be required."