Based on the 2020 NEC.
Question: Are wireways permitted to pass through a wall or must they remain exposed for the entire run?
See answer below.
Answer: Yes
Explanation: Section 376.10(4) and 378.10(4) both permit a wireway to pass through a wall as long as the conductors remain accessible on each side of the wall and the section passing through the wall is unbroken.
John Lupacchino is a senior design engineer with Gaylor Electric, Inc. in Noblesville, Ind. and serves as an alternate on NEC Code-Making Panel No. 3. He is currently licensed in more than 80 jurisdictions. He can be reached at [email protected].