Question: What is the maximum length of a vertical run of conduit containing 500kcmil copper conductors that does not require supporting the individual conductors in the raceway?
- 10 ft
- 20 ft
- 30 ft
- 50 ft
See the answer below.
Answer: 50 ft
Explanation: Section 300.19(A) requires support of conductors in vertical raceways if the vertical rise exceeds the values shown in Table 300.19(A). Additional intermediate supports are required to limit supported conductor lengths to not greater than those values specified in Table 300.19(A).
Lupacchino is a senior design engineer with Gaylor Electric, Inc. in Noblesville, Ind. and serves as an alternate on NEC Code-Making Panel No. 3. He is currently licensed in more than 80 jurisdictions. He can be reached at [email protected].