Moving Violations Video No. 316: Panelboard Problems
Aug. 1, 2024
In this edition of Moving Violations, Russ looks at a panelboard with multiple problems. First, the lack of seals is a violation of Sec. 110.12(A). Second, the locknuts in the installation aren’t attached, which violates the requirements of Art. 250. Also, the cables in the installation are not mechanically secured, which violates Sec. 300.10. Watch the video and check out the violations for yourself. Do you see any other concerns that Russ didn’t mention?