What's Wrong Here?

Dec. 1, 2003
Hint: Has anyone seen an exit sign? How are you supposed to get out of this parking garage?

How well do you know the Code? Think you can spot violations the original installer either ignored or couldn't identify? Here's your chance to moonlight as an electrical inspector and second-guess someone else's work from the safety of your living room or office. Joe Tedesco, who has a knack for finding shoddy electrical work, did the dirty work and found this mess. Now it's your turn to identify the violation.

Find the Answer

Herb Hartley, president, Hartley Electric & Alarm Co., Inc., Sims, N.C., pointed out that the electrical metallic tubing(EMT) is improperly connected to the sign. The conductors aren't housed in abox or placed within the sign enclosure, and there are exposed open splices. The water or sprinkler pipe is also blocking the exit sign, clearly a violation of the Life Safety Code, NFPA 101, 2000 Edition Chapter 7, which states “the signshall be clearand visible.”

Thomas Blalock, maintenance manager, Allen Family Foods, Laurel, Del., and Jean-Jacques Ahounou, electrical engineer, EIT, Highland Associates, New York City, also note that neither the exit sign is illuminated nor the raceway is properly terminated or secured, setting up an improper grounding situation and exposed live wires.

Per 358.2, EMT is defined as “an unthreaded thinwall raceway of circular cross section designed for the physical protection and routing of conductors and cables and for use as an equipment grounding conductor when installed utilizing appropriate fittings.”

About the Author

Joe Tedesco

Tedesco served the industry in many roles during his career. He was a director, senior electrical code instructor for National Technology Transfer, Inc. and American Trainco, Inc.. He was also a codes, standards and seminar specialist for the International Association of Electrical Inspectors and an electrical field service specialist for the National Fire Protection Association in Quincy, Mass. He ran his own business as an NEC consultant and is a Massachusetts licensed master electrician and journeyman electrician and certified electrical inspector (one and two family 2A; General 2B, and Plan Review, 2C). Tedesco also wrote articles for CEE News and EC&M (Code Violations Illustrated and What's Wrong Here?) for more than 15 years and helped launched the Moving Violations video series.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Don't Let Burn-Through Threaten Another Data Center or Utility Project

Get the No Burn-Through Elbow eGuide to learn many reasons why Champion Fiberglass elbows will enhance your data center and utility projects today.

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.