Whats Wrong Here?

What is in this article?:

Find the Answer

This walkway lighting system must have been installed by someone who was not familiar with the accepted methods used in the electrical industry. Open nonmetallic conduit of this type with energized and exposed supply conductors shows no knowledge of electrical safety or Code requirements.

 

Underground sections of conduit buried to proper depths (according to 300.5) and extended into the bottom of the pole (where the splices will be accessible) would have been the proper way to supply this lighting unit. See 410.30(B) for a list of the six requirements that must be met when installing metal poles to support luminaires (i.e., lighting fixtures) and serve as a raceway to enclose supply conductors.