What’s Wrong Here? Hint: Don't Blow a Gasket

What is in this article?:

Can you identify the Code violation(s) in this photo?

 

How well do you know the Code? Think you can spot violations the original installer either ignored or couldn't identify? Here's your chance to moonlight as an electrical inspector and second-guess someone else's work from the safety of your living room or office. It's your turn to identify the violation.

Hint: Don't blow a gasket.

Discuss this Article 9

Anonymous (not verified)
on Dec 6, 2012

No Strap

BXNPTWR (not verified)
on Dec 6, 2012

NEMA 1 cover in outdoor location.

Aaron (not verified)
on Dec 6, 2012

Nema 1 cover used in incorrect application (outdoor use). Sealtite not secured.

Anonymous (not verified)
on Dec 6, 2012

no water sealing/rainproof gasket between box & conduit at top

Tom (not verified)
on Dec 7, 2012

Missing a gasket, and correct weatherproof plate sealtight is not straped to the buiding within 12 inches to the plate

Anonymous (not verified)
on Dec 7, 2012

The cover is not a w/p and does not have a gasket.

Anonymous (not verified)
on Dec 8, 2012

Not a weatherproof cover

mrsafetyman
on Dec 11, 2012

both the box and cover must be rated for Wet Location and yes sealtite needs to be supported with a strap I like 6 inches from box

Anonymous (not verified)
on Dec 12, 2012

What about he flex rubbing against the brick edge? Is there a workmanship issue about protecting the plastic flex from being abraded away?

Post new comment
Sign In or register to use your Electrical Construction & Maintenance (EC&M) Magazine ID
(optional)

White Papers
EC&M Learning Center
Webinars
EC&M TV
Apr. 15, 2013
video

Westex Flash Fire Testing Overview

See side-by-side comparisons of different flame resistant fabrics exposed to flash fires, illustrating the extent, severity and location of burns....More

Newsletter Signup

Connect With Us