What’s Wrong Here? Hint: A Bundle of Joy

What is in this article?:

Can you identify the Code violation(s) in this photo?

Find the Answer

While this bundle itself is not a violation, the NM cable used to support the whole bundle is most certainly a Code violation. Section 300.11(C) prohibits cable wiring methods from being used "as a means of support for other cables, raceways, or nonelectrical equipment."

In this installation, there are only a couple of NM cables stapled to the side of the joist, and all of the other NM cables are bundled and secured to those original cables. This could cause damage to the stapled cables, since it adds significant weight onto the cable jacket, insulation, and conductors of the original cables. This can be a common problem where installers simply run out of room to staple any more cables onto the beam. Instead of installing running boards or using a different joist, installers will mistakenly tie-wrap cable after cable onto those that were originally stapled to the beam.

Although bundling of NM cables is not a violation of the Code, installers must also be aware of the requirements to adjust the ampacity of the conductors in accordance with 310.15(B)(3). Where single or multi-conductor cables are installed similar to this installation, "longer than 24 in. without maintaining spacing," the allowable ampacity of each conductor shall be reduced in accordance with table 310.15(B)(3)(a).

> Try Another Quiz

Discuss this Article 5

Anonymous (not verified)
on Jan 3, 2013

It also looks like there is a single gang device box on the left hand side with an octagon cover plate.

Anonymous (not verified)
on Jan 3, 2013

How do you know it's wrong?? Maybe there was LOTS of derating done.... 9A breakers?? Just kidding...

CW Muse (not verified)
on Jan 7, 2013

At least they did a neat job and the cable coming from the box on the left is not secured.

Anonymous (not verified)
on Jan 7, 2013

current will be induced into ajoining cables if they are bundled together, causing interference.

Anonymous (not verified)
on Jan 8, 2013

electrical wires strapped close to what it seems metal pipes what does it carry? in the left conner is that a trunking race-way left uncovered? i would prefer to encase the wire in some sort of race-way conduit, trunking because of the surroundings the flooring is wood aswell

Post new comment
Sign In or register to use your Electrical Construction & Maintenance (EC&M) Magazine ID
(optional)

White Papers
EC&M Learning Center
Webinars
EC&M TV
Apr. 15, 2013
video

Protection From Arc Flashes

Learn how arc flashes happen, how they are measured and how wearing the right flame resistant clothing can keep workers safe....More

Newsletter Signup

Connect With Us