Illustrated Catastrophes

Dec. 1, 2007
As usual, never consider the following commentary associated with these photos as a formal interpretation of the National Electrical Code (NEC). Without criticizing anyone or any product, the following scenarios present us with serious safety questions. All references are based on the 2005 NEC. ARCHITECTURALLY APPEALING, BUT ELECTRICALLY DEFICIENT Franco Loughnan Morneault, owner, Construction and

As usual, never consider the following commentary associated with these photos as a formal interpretation of the National Electrical Code (NEC). Without criticizing anyone or any product, the following scenarios present us with serious safety questions.

All references are based on the 2005 NEC.

Architecturally Appealing, But Electrically Deficient

Franco Loughnan Morneault, owner, Construction and Remodeling, Brooklyn and Staten Island, N.Y., snapped these photos at a luxury house that sold for $2.2 million about 18 months ago. “The house is located in a vacation community on Fire Island,” says Morneault. “When it was built back in 1985, it graced six pages of Architectural Digest magazine. We're gutting it out in the fall.”

Here are the Code violations he noted at this location.

“The sticker on the main panelboard rates it for 40 circuit breaker poles. I counted 61! A second panelboard (the house has 400A service) is half empty. It only had 21 circuit breakers in it. The half-empty panelboard is located in the basement, and this overflowing panelboard is located in the laundry room.

“The two photos taken under the deck show a nice spiderweb pattern. I especially like the hanging junction boxes, and the way somebody left one open, not even bothering to tuck the wires into the box.

“Garden lighting is located under a walk leading up to the deck. Aren't these conductors supposed to be buried or placed in conduit? This is pretty typical of what I saw throughout the property. Where I did find buried wires, they were typically placed only 3 or 4 inches below the surface, and otherwise unshielded.

“Although there were more, these were the most obvious violations I documented.”

Here are some specific Code references we can relate to this particular installation.

As per 408.35, “Not more than 42 overcurrent devices (other than those provided for in the mains) of a lighting and appliance branch-circuit panelboard shall be installed in any one cabinet or cutout box. A lighting and appliance branch-circuit panelboard shall be provided with physical means to prevent the installation of more overcurrent devices than that number for which the panelboard was designed, rated, and approved. For the purposes of this article, a 2-pole circuit breaker shall be considered two overcurrent devices; a 3-pole circuit breaker shall be considered three overcurrent devices.”

As per 300.11(A), “Raceways, cable assemblies, boxes, cabinets, and fittings shall be securely fastened in place.”

As per 340.10, “Type UF cable shall be permitted as follows:

“(1) For use underground, including direct burial in the earth. For underground requirements, see 300.5.

“(3) For wiring in wet, dry, or corrosive locations under the recognized wiring methods of this Code.”

Found a Code violation? E-mail your text and photos (no cell phone images, please) to Joe Tedesco at [email protected].

About the Author

Joe Tedesco

Tedesco served the industry in many roles during his career. He was a director, senior electrical code instructor for National Technology Transfer, Inc. and American Trainco, Inc.. He was also a codes, standards and seminar specialist for the International Association of Electrical Inspectors and an electrical field service specialist for the National Fire Protection Association in Quincy, Mass. He ran his own business as an NEC consultant and is a Massachusetts licensed master electrician and journeyman electrician and certified electrical inspector (one and two family 2A; General 2B, and Plan Review, 2C). Tedesco also wrote articles for CEE News and EC&M (Code Violations Illustrated and What's Wrong Here?) for more than 15 years and helped launched the Moving Violations video series.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Don't Let Burn-Through Threaten Another Data Center or Utility Project

Get the No Burn-Through Elbow eGuide to learn many reasons why Champion Fiberglass elbows will enhance your data center and utility projects today.

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.