Comments Feed

NEMA General-Purpose Contactors Switching Dry Type Transformers Commented on: 42 weeks ago (November 6, 2015)

Having worked with motors, I've learned a lot about inrush currents so I understand the reasoning. I do have one question though. You mention a three-phase contactor. I've always called them three...

What’s Wrong Here? Hint: It’s as Plain as Black and White Commented on: 1 year ago (June 25, 2015)

I agree with Robert Masters. The white wire can only legally be used as a neutral and must not be fused.

Code Q&A: Wiring Methods Allowed in Hazardous Locations Commented on: 2 years ago (May 11, 2014)

You left out one of the most common hazardous locations covered under Article 514 -- Gas Stations and fuel dispensing areas. One of the most enjoyable type of work areas when you understand the...

What’s Wrong Here? Hint: Funny Looking Service Disconnect Commented on: 2 years ago (April 25, 2014)

It's hard to tell what is going on here from this picture. It appears that a ground bar was needed for something, we cannot see where the bare ground wire is going. Is the bare wire grounding...

What’s Wrong Here? Hint: Wet Behind the Ears Commented on: 2 years ago (April 25, 2014)

I see mentioned several times that a compression EMT fitting is needed here. Actually the old compression fittings are concrete tight and no longer are considered water tight. The new water tight...

What’s Wrong Here? Hint: Beware of What Lurks Below the Surface Commented on: 2 years ago (April 25, 2014)

Actually I see no reason for these conduit bodies to even be installed. If they were used to make splices, then we have a reason, but these do not meet criteria for splice boxes. Were they used as...

Minimum Number of Outlets Commented on: 2 years ago (March 7, 2014)

Anything that keeps us thinking about codes and code changes is a good idea.

What’s Wrong Here? Hint: Danger Island Commented on: 2 years ago (February 20, 2014)

They don't abide by the NEC over there.

Electrical Testing Feed
Join the Discussion on EC&M Talk

EC&M Webinars
Jul 28, 2016
Sponsored

Next Generation Lighting- The Emergence of POE for Lighting

Historically, lighting controls have always had a singular responsibility: Manage the light. Until now....More
Jul 21, 2015
Sponsored

ON DEMAND: Mitigation Methods for Arc Flash Hazards - Enhancing Personal Safety

The energy released during an arc flash event can result in severe damage to personnel, equipment, and property. While there are solutions which seek to improve the protection for each, this program will focus on personnel....More
EC&M Learning Center

Connect With Us

Sponsored Introduction Continue on to (or wait seconds) ×