The Basics of Vector Analysis Part 4

The Basics of Vector Analysis Part 1
The Basics of Vector Analysis Part 2
The Basics of Vector Analysis Part 3

Fig. 1. A 3-phase, 4-wire circuit in which there are only two phase-to-neutral loads.

Last month, we showed how you could use vector diagrams and simple math to calculate neutral currents in 3-phase, 4-wire circuits. In this last installment, we'll talk about using simple parallelogram relationships and trigonometry to determine neutral currents in balanced and unbalanced circuits.

Fig. 2. Because there is no Phase C-to-neutral load, the Phase C current is zero, and the resulting vector diagram shows only phase vectors A and B, 120° apart.

Suppose you have a 3-phase, 4-wire circuit in which there are only two phase-to-neutral loads, as shown in Fig. 1. In addition, one of these loads varies. How can you calculate the neutral current by using vectors?

Because there is no Phase C-to-neutral load, the Phase C current is zero, and the resulting vector diagram will show only phase vectors A and B, 120¡ã apart, as shown in Fig. 2. And because the Phase A-to-neutral load is fixed, we know that the Phase A current is 10A.

Fig. 3. Typical parallelogram diagram.

As the Phase B-to-neutral load varies, the neutral current also will vary. Let's start with a Phase B current of 10A. We know from Problem 1 of the Part 3 installment in the October 2008 issue that the neutral current also is 10A. This is because the phase vectors A and B are of equal magnitude. By drawing dotted lines parallel and of equal length to these vectors, we create a parallelogram having equal sides. When we draw the neutral vector N, we divide the parallelogram exactly in half and create an equilateral triangle ¡ª one in which all sides are of equal length (magnitude here), and all interior angles are 60¡ã. Therefore, the resultant vector N also will have the same magnitude as phase vectors A and B.

How about when the Phase B current equals zero? Well, in this instance, the system effectively becomes single-phase, and the neutral current is again 10A.

Fig. 4. Vector diagram showing varying phase vectors B (as per varying Phase B-to-neutral load) and resulting neutral current vectors N.

For the Phase B currents between zero and 10A, we can use some trigonometry and equations applicable to parallelograms to calculate the respective neutral currents. First, let's draw a typical parallelogram, as shown in Fig. 3, with sides A and B. To find the length of the diagonal line P, we use the following equation:

P = ¡Ì [ (A2 + B2) - (2AB cos ¦È) ] (Equation1)

Keeping the above equation in mind, let's draw a vector diagram, as shown in Fig. 4, and assume Phase B current is 7.5A. What will the neutral current be?

Using Equation 1, you substitute 10A for ¡°A¡± and 7.5A for ¡°B¡±. We know the angle is 60¡ã, and we determine that cos 60¡ã is .500 from a trigonometric table. The resulting calculation is as follows:

N7.5 = ¡Ì(A2 + B2 -2AB cos ¦È)

= ¡Ì [ (102 + 7.52) - (2 ¡Á 10 ¡Á 7.5 ¡Á .500) ]

= ¡Ì [ (100 + 56.25) - 75 ]

= ¡Ì 81.25 ¡Ö 9A

By substituting differing values for Phase B current in Equation 1, you can obtain the respective neutral currents. For example, if the Phase B current is 5A, the calculation results in a neutral current (N5) of 8.66A. For a Phase B current of 2.5A, the neutral current (N2.5) again will be approximately 9A.


Want to use this article? Click here for options!





Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

May 10, 2012 12:44 PM

What's Wrong Here?

Apr 19, 2012 10:09 AM

What's Wrong Here?

Apr 5, 2012 2:27 PM

View all What's Wrong Here?

product spotlight

EV charger tester

May 25, 2012 8:26 AM

EV charger tester

The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M Whitepaper

Arc Mitigation –A Three-Step Approach

Did you know that an arc-flash incident hospitalizes 5-7 workers per day in North America, severely impacting processes and profitability with lost production? Download This Sponsored Whitepaper Today!

What's New in Residential Cabling?
Date: Wednesday, May 30, 2012
Time: 2:00pm ET


In this The Home Depot sponsored Low Voltage Webinar, Ron Kipper RCDD / NTS will discuss the need for compression style coaxial connectors and the migration of the entire CATV, Satellite and Audio / Video industry to them. Register Today!

Grounding Versus Bonding
Now Available On-Demand


In this 60-minute FREE webinar, Mike Holt of Mike Holt Enterprises, Inc. will explain the purpose of grounding and bonding as related to the most current requirements set forth in the 2011 NEC. Register to View On-Demand!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues