Code Quiz: Snap Switches

March 6, 2013
NEC guidelines on snap switches

Fill in the blanks with the appropriate answer.

A snap switch rated 30A, directly connected to aluminum conductors, shall be ______ and marked _______.

A. identified / CU/AL

B. identified / copper only

C. listed / CO/ALR

D. none of the above

Answer: D

Section 404.14(C) does not address 30A rated snap switches. This section of the Code does address snap switches rated 20A or less directly connected to aluminum conductors, which shall be listed and marked CO/ALR.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.