Fill in the blank with the appropriate answer.
When installing a single rigid metal or intermediate metal conduit to support a pendant box that supports a luminaire, the threaded joints shall be prevented from loosening by _______.
A. set screws or other effective means
B. placing the luminaire so at any point it shall be at least 8 ft or more above grade or standing area, and 3 ft horizontally from the 8 ft vertical elevation from windows, doors, porches, fire escapes and similar locations
C. “double-cut zigzag” threads
D. Either A or B
Find the Answer
Answer: D
As noted in Sec. 314.23(H)(2), where supported only by a single conduit, the threaded joints shall be prevented from loosening by set screws or other effective means, or the luminaire at any point shall be at least 8 ft or more above grade or standing area, and 3 ft horizontally from the 8 ft vertical elevation from windows, doors, porches, fire escapes and similar locations.