Code Quiz: Instrumentation Tray Cable

Fill in the blank with the appropriate answer.

Type ITC cables (instrumentation tray cable) shall not be installed with power, lighting, or Class 1 circuits that are not power limited, or non-power-limited circuits, except ___________ .

A. where terminated within equipment or junction boxes and separations are maintained by insulating barriers or other means.

B. where a metallic sheath or armor is applied over the nonmetallic sheath of the Type ITC cable.

C. as permitted by A or B.

Answer: C

As noted in 727.5 of the 2011 NEC, "Type ITC cables shall not be installed with power, lighting, Class 1 circuits that are not power limited, or non-power-limited circuits." The two exceptions to this rule read as follows:

"Exception No. 1: Where terminated within equipment or junction boxes and separations are maintained by insulating barriers or other means."

"Exception No. 2: Where a metallic sheath or armor is applied over the nonmetallic sheath of the Type ITC cable."