Code Quiz: GFCI Protection

April 10, 2014
NEC guidelines on GFCI protection on equipment without cord and plug connection

Q. Which of the following items may be wired directly (i.e., hard-wired) without cord-and-plug connection, thus omitting the requirement for GFCI protection?

A. Vending machines

B. Electric drinking fountains

C. Electric automotive vacuum machines and tire inflation machines provided for public use

D. Dishwasher in a kitchen

E. None of the above

Find the Answer

Answer: E

With respect to the equipment listed in the question, it does not matter whether the equipment is cord-and-plug connected or wired directly without cord-and-plug connection; GFCI protection is required for all items listed. See Sections 210.8(D), 422.23, 422.51, and 422.52 of the 2014 NEC.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

Champion Strut Catalog

Champion Fiberglass is the most advanced manufacturing facility of fiberglass conduit, fiberglass bridge drain and fiberglass strut systems in the world. Its well-trained and ...

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...

Xpress Elbows Guide for Industrial Construction

Learn how to get expedited elbows shipped within 2 days.