When are low-voltage control equipment, relays, motors and the like permitted to be installed in compartments with exposed high-voltage energized parts or high-voltage wiring with respect to equipment that is operating at over 600V?
- When the access means is interlocked with the high-voltage switch or disconnecting means to prevent the access means from being opened or removed.
- When the high-voltage switch or disconnecting means is in the isolating position.
- Option A or B is permitted
- It is never permitted to do this in applications over 600V nominal
Answer: C
As noted in 490.35(B), "Low-voltage control equipment, relays, motors and the like shall not be installed in compartments with exposed high-voltage energized parts or high-voltage wiring unless either of the following conditions is met:
- The access means is interlocked with the high-voltage switch or disconnecting means to prevent the access means from being opened or removed.
- The high-voltage switch or disconnecting means is in the isolating position.