Code Quiz

Dec. 17, 2009
When working with electrical systems, including multi-conductor cables, identification of conductors is an important issue.


Fill in the blank

When working with electrical systems, including multi-conductor cables, identification of conductors is an important issue. For example, on a new 480/277V, 3-phase, 4-wire system, the NEC requires you to identify conductors by phase or line and system [210.5(C)]. It is common practice to identify these ungrounded conductors with an outer finish (i.e., insulation color) that is: brown, orange, and yellow; gray for the grounded conductor; and green, green with one or more yellow stripes, or bare for the equipment grounding conductor. But when working on existing electrical systems, such as 480/277V, 3-phase, 4-wire systems, you should take care because the color __________ may have been used for an ungrounded conductor. Hint: See the Fine Print Note.

  1. white
  2. white with one or more colored stripes, other than green
  3. black with three distinctive white stripes on its entire length
  4. gray

Answer: D

As noted in the Fine Print Note of 200.6(E), "The color gray may have been used in the past as an ungrounded conductor. Care should be taken when working on existing systems." Although the FPN is cautioning electricians to be aware of the conductor with the outer gray color, it's possible that other colored conductors that are not normally used to identify ungrounded conductors may have been used as ungrounded conductors. So be careful out there!

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.