In accordance with Art. 800, when installing communications wires and cables in a raceway, what is the maximum percent fill permitted in EMT?
- 53% from Chapter 1, Table 9
- 40% from Chapter 1, Table 9
- 31% from Chapter 1, Table 9
- unlimited number of wires or cables, as the requirements of Chapter 3 or Chapter 9 do not apply.
Answer: D
As noted in 800.110(B), "the raceway fill requirements of Chapters 3 and 9 shall not apply to communications wires and cables."