In a surface metal raceway that measures 4 in. by 2 in., what is the maximum number of 12 AWG THHN, 600V insulated, single conductors, operating at 480V nominal permitted?

In a surface metal raceway that measures 4 in. by 2 in., what is the maximum number of 12 AWG THHN, 600V insulated, single conductors, operating at 480V nominal permitted? The surface metal raceway is designed to contain a maximum of 255 conductors, and the thickness of the metal is 0.040 in. nominal.

  1. 60
  2. 120
  3. 255
  4. It is not permitted to install conductors operating at 300V or more in a surface metal raceway.

Answer: C

Assuming a 20% fill, the number of conductors allowed is calculated as follows:

  1. 4 in. x 2 in. = 8 sq. in. (total sq. in. area)
  2. 20% (fill allowed) x 8 = 1.6 sq. in. (maximum usable space allowed)
  3. 1.6 sq. in. ÷ 0.0133 (sq. in. area for a single 12 AWG THHN conductor from Chapter 9, Table 5) = 120 (maximum number of conductors allowed)
However, the surface metal raceway is designed for a maximum of 255 - 12 THHN or THWN conductors. Therefore, the maximum number of conductors allowed is actually 255 (per the manufacturer's design).

Reference NEC Secs. 386.10, 386.12, 386.22, and Table 5 in Chapter 9.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...