Code Quiz

Jan. 6, 2011
New requirements for marking of cable trays apply when the cable trays installed within substations contain conductors _________.

Fill in the blanks with the correct answers. New requirements for marking of cable trays apply when the cable trays installed within substations contain conductors _________. The warning notice shall be installed in a conspicuous position along the cable tray at intervals not to exceed ____ ft.

  1. with 600V insulation; 20
  2. cable tray rated; 50
  3. rated higher than 600V; 10
  4. rated higher than 35kV; 20

Answer: C

A new section has been added to Art. 225 of the 2011 NEC. Section 225.70 outlines the warning sign requirements in substations. The term "substation" is also a new definition in Art. 100.

As noted in 225.70(A)(1)(c), a "DANGER — HIGH VOLTAGE" sign shall be placed "on all cable trays containing high-voltage conductors with the maximum spacing of warning notices not to exceed 10 ft." ANSI Z-535.2 or ANSI Z-535.4 may also provide guidelines for the warning notice.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.