Code Quiz

Q. When are conductors permitted to be terminated based on the 90°C temperature rating and ampacity as given in Table 310.60(C)(67) through Table 310.60(C)(86)?

 

 

 

  1. Conductors are only permitted to be terminated based on 60°C temperature and ampacity ratings.
  2. Conductors are only permitted to be terminated based on 75°C temperature and ampacity ratings.
  3. Conductors are permitted to be terminated based on 90°C temperature and ampacity ratings in accordance with 110.40.
  4. It is not permitted in the NEC.

Answer: C

As noted in 110.40, it is permitted to terminate conductors based on the 90°C temperature rating and ampacity as given in Table 310.60(C)(67) through 310.60(C)(86). This differs from the requirements in 110.14(C)(1), which will not allow this.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at necexpert@aol.com.

Discuss this Article 3

Anonymous (not verified)
on Jun 22, 2012

The last sentence in the answer to this question is misleading - "This differs from the requirements in 110.14(C)(1), which will not allow this." 110.14(C)(1) does not precluded terminating conductors at 90degC as this section includes the following qualifier "Unless the equipment is listed and marked otherwise,..." Therefore if the equipment is listed and marked for 90degC terminations (i.e. MV switchgear) 110.14(C)(1) does not precluding the use of 90degC ampacities.

Robert Azulay (not verified)
on Jun 22, 2012

Art 110-40 is for circuits rated over 600 volts. It doesn't apply M.V. circuits. 110-14(c)1 and all the exceptions clearly explains the procedure for calculating and installing the proper conductors at their proper ampacity's.

Anonymous (not verified)
on Oct 28, 2012

The question asks "when". Answer C. does not clearly answer the question because it does not include "unless otherwise identified"

Post new comment
Sign In or register to use your Electrical Construction & Maintenance (EC&M) Magazine ID
(optional)

White Papers
EC&M Learning Center
Webinars
EC&M TV
Apr. 15, 2013
video

The Westex Difference

Learn what sets Westex apart from other flame resistant fabric manufacturers....More

Newsletter Signup

Connect With Us