Code Quiz

April 3, 2008
When installing wiring methods in ducts or plenums used for environmental air, all but which of the following wiring methods are permitted?

Q. When installing wiring methods in ducts or plenums used for environmental air, all but which of the following wiring methods are permitted?

  1. Flexible metal conduit no greater than 4 feet in length
  2. EMT
  3. IMC
  4. MC cable with overall nonmetallic covering

Answer: D

Per 300.22(B), outer nonmetallic coverings are not permitted in this type of installation. This correlates with the requirements of 300.21, which focuses on the topic of Spread of Fire or Products of Combustion.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...