Stumped by the Code? Sizing Overcurrent Protection for Branch Circuits, Class III Hazardous (Classified) Location, Minimum Clearances of Overhead Feeder Conductors, and More

Aug. 15, 2013
Your most pressing National Electrical Code (NEC) questions answered

All questions and answers are based on the 2011 NEC.

Q. What is the Code rule for sizing overcurrent protection for branch circuits [210.20]?

A. Branch circuit overcurrent devices must have a rating of not less than 125% of the continuous loads, plus 100% of the noncontinuous loads [210.20(A)], as shown in the Figure. Branch-circuit conductors must be protected against overcurrent in accordance with 240.4 [220.20(B)].

Branch circuit overcurrent protection requirements are noted in Sec 210.20.



Q. When are receptacles required to be tamper-resistant?

A. All nonlocking type 15A and 20A, 125V receptacles in the following areas of a dwelling unit [210.52] must be listed as tamper-resistant [406.12]:
• Wall space — 210.52(A)
• Small appliance circuit — 210.52(B)
• Countertop space — 210.52(C)
• Bathroom area — 210.52(D)
• Outdoors — 210.52(E)
• Laundry area — 210.52(F)
• Garage and outbuildings — 210.52(G)
• Hallways — 210.52(H)
Receptacles in the following locations are not required to be tamper-resistant [406.12 Ex.]:
• Receptacles located more than
5½ ft above the floor.
• Receptacles that are part of a luminaire or appliance.
• A receptacle located within dedicated space for an appliance that in normal use isn’t easily moved from one place to another.
• Nongrounding receptacles used for replacements as permitted in 406.4(D)(2)(a).

Q. What is a Class III Hazardous (Classified) location?

A. A Class III location is an area where easily ignitable fibers or materials producing combustible flyings are handled, manufactured, or used — and aren’t likely to be suspended in the air in quantities sufficient to produce ignitable mixtures [500.5(D)]. A Class III, Div. 1 location is an area where ignitable fibers/flyings are manufactured, handled, or used, such as within textile mills or clothing manufacturing plants, as well as in facilities that create sawdust and flyings by pulverizing or cutting wood [500.5(D)(1)]. A Class III, Div. 2 location is an area where ignitable fibers/flyings are stored or handled other than in the manufacturing process [500.5(D)(2)].

Q. What does the Code require for minimum clearances of overhead feeder conductors?

A. Overhead conductor spans must maintain vertical clearances as follows [225.18]:
1)    10 ft above finished grade, sidewalks, platforms, or projections from which they might be accessible to pedestrians for 120V, 120/208V, 120/240V, or 240V circuits.
2)    12 ft above residential property and driveways, and those commercial areas not subject to truck traffic for 120V, 120/208V, 120/240V, 240V, 277V, 277/480V, or 480V circuits.
4)    18 ft over public streets, alleys, roads, parking areas subject to truck traffic, driveways on other than residential property, and other areas traversed by vehicles (such as those used for cultivation, grazing, forestry, and orchards).
5)    24½ ft over track rails of railroads.
Note: Overhead conductors located above pools, outdoor spas, outdoor hot tubs, diving structures, observation stands, towers, or platforms must be installed in accordance with the clearance requirements in 680.8.   

About the Author

Mike Holt

Mike Holt is the owner of Mike Holt Enterprises (www.MikeHolt.com), one of the largest electrical publishers in the United States. He earned a master's degree in the Business Administration Program (MBA) from the University of Miami. He earned his reputation as a National Electrical Code (NEC) expert by working his way up through the electrical trade. Formally a construction editor for two different trade publications, Mike started his career as an apprentice electrician and eventually became a master electrician, an electrical inspector, a contractor, and an educator. Mike has taught more than 1,000 classes on 30 different electrical-related subjects — ranging from alarm installations to exam preparation and voltage drop calculations. He continues to produce seminars, videos, books, and online training for the trade as well as contribute monthly Code content to EC&M magazine.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Don't Let Burn-Through Threaten Another Data Center or Utility Project

Get the No Burn-Through Elbow eGuide to learn many reasons why Champion Fiberglass elbows will enhance your data center and utility projects today.

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.