Code Q&A

Jan. 20, 2011
Q. When can I use Table 310.15(B)(6)?

Q. When can I use Table 310.15(B)(6)?

A. For individual dwelling units of one-family, two-family, and multifamily dwellings, Table 310.15(B)(6) can be used to size 3-wire, single-phase, 120/240V service or feeder conductors that supply all loads that are part of or associated with the dwelling unit.

The 120/208V, single-phase feeders from a 120/208V, 3-phase service are sometimes used to supply single-family dwelling units in a multifamily building, and this table can't be used when that is done. Table 310.16 must be used when that is the case.

Feeder conductors are not required to have an ampacity rating more than the service conductors [215.2(A)(3)].

Warning: Table 310.15(B)(6) doesn't apply to 3-wire, single-phase, 120/208V systems, because the neutral conductor in these systems carries neutral current even when the load on the phases is balanced [310.15(B)(4)(6)]. For more information on this topic, see 220.61(C)(1).

About the Author

Mike Holt

Mike Holt is the owner of Mike Holt Enterprises (www.MikeHolt.com), one of the largest electrical publishers in the United States. He earned a master's degree in the Business Administration Program (MBA) from the University of Miami. He earned his reputation as a National Electrical Code (NEC) expert by working his way up through the electrical trade. Formally a construction editor for two different trade publications, Mike started his career as an apprentice electrician and eventually became a master electrician, an electrical inspector, a contractor, and an educator. Mike has taught more than 1,000 classes on 30 different electrical-related subjects — ranging from alarm installations to exam preparation and voltage drop calculations. He continues to produce seminars, videos, books, and online training for the trade as well as contribute monthly Code content to EC&M magazine.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.