Stumped by the Code? Rules for the identification of branch circuit conductors

Dec. 15, 2016
Your most pressing National Electrical Code (NEC) questions answered

Q. What are the Code rules for the identification of branch circuit conductors?

A. The neutral conductor of a branch circuit must be identified in accordance with Sec. 200.6 [210.5(A)].

Equipment grounding conductors can be bare, covered, or insulated. Insulated equipment grounding conductors size 6 AWG and smaller must have a continuous outer finish either green or green with one or more yellow stripes [250.119]. On equipment grounding conductors 4 AWG and larger, insulation can be permanently re-identified with green marking at the time of installation at every point where the conductor is accessible [250.119(A)].

If the premises wiring system contains branch circuits supplied from more than one voltage system, each ungrounded conductor must be identified by phase and system at all termination, connection, and splice points in accordance with 210.5(C)(1)(a) and (b) (see Figure). Identification can be by color-coding, marking tape, tagging, or other means approved by the authority having jurisdiction. The method of identification must be documented in a manner that’s readily available or permanently posted at each branch-circuit panelboard.

Marking can be done by posting an identification legend that explains the method used.

When a premises has more than one voltage system supplying branch circuits, the ungrounded conductors must be identified by phase and system. This can be done by permanently posting an identification legend that describes the method used, such as color-coded marking tape or color-coded insulation. Conductors with insulation that’s green or green with one or more yellow stripes can’t be used for an ungrounded or neutral conductor [250.119].

Although the NEC doesn’t require a specific color code for ungrounded conductors, electricians often use the following color system for power and lighting conductor identification:

120/240V, single-phase — black, red, and white

120/208V, 3-phase — black, red, blue, and white

120/240V, 3-phase — black, orange, blue, and white

277/480V, 3-phase — brown, orange, yellow, and gray; or, brown, purple, yellow, and gray

Q. What are the Code requirements for the location of overcurrent devices?

A. Circuit breakers and fuses must be readily accessible, and they must be installed so the center of the grip of the operating handle of the fuse switch or circuit breaker, when in its highest position, isn’t more than 6 ft, 7 in. above the floor or working platform, unless the installation is for [240.24(A)]:

(1) Busways, as provided in Sec. 368.17(C).

(2) Supplementary overcurrent devices aren’t required to be readily accessible [240.10].

(3) For overcurrent devices, as described in Sec. 225.40 and Sec. 230.92.

(4) Overcurrent devices located next to equipment can be mounted above 6 ft, 7 in., if accessible by portable means [404.8(A), Exception No. 2].

As noted in Sec. 240.24(C), overcurrent devices must not be exposed to physical damage. An Informational Note also says that electrical equipment must be suitable for the environment, and consideration must be given to the presence of corrosive gases, fumes, vapors, liquids, or chemicals that have a deteriorating effect on conductors or equipment [110.11].

Overcurrent devices must not be located near easily ignitable material, such as in clothes closets, and they aren’t permitted to be located in the bathrooms of dwelling units, dormitories, or guest rooms or guest suites of hotels or motels. Note: The service disconnecting means must not be located in a bathroom, even in commercial or industrial facilities [230.70(A)(2)].

Overcurrent devices must not be located over the steps of a stairway. Note: It’s difficult for electricians to safely work on electrical equipment located on uneven surfaces like stairways.

These materials are provided to us by Mike Holt Enterprises in Leesburg, Fla. To view Code training materials offered by this company, visit www.mikeholt.com/code

About the Author

Mike Holt

Mike Holt is the owner of Mike Holt Enterprises (www.MikeHolt.com), one of the largest electrical publishers in the United States. He earned a master's degree in the Business Administration Program (MBA) from the University of Miami. He earned his reputation as a National Electrical Code (NEC) expert by working his way up through the electrical trade. Formally a construction editor for two different trade publications, Mike started his career as an apprentice electrician and eventually became a master electrician, an electrical inspector, a contractor, and an educator. Mike has taught more than 1,000 classes on 30 different electrical-related subjects — ranging from alarm installations to exam preparation and voltage drop calculations. He continues to produce seminars, videos, books, and online training for the trade as well as contribute monthly Code content to EC&M magazine.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.