Q. How do I size the equipment grounding conductor to a motor branch circuit? A. Equipment grounding conductors of the wire type must be sized not smaller than shown in Table 250.122, based on the rating of the circuit overcurrent device; however, the circuit equipment grounding conductor isn’t required to be larger than the circuit conductors [250.122(A)] (Table). Section 250.122(D)(1) specifically addresses sizing the equipment grounding conductor for motor branch ...