How well do you know the Code? Think you can spot violations the original installer either ignored or couldn't identify? Here's your chance to moonlight as an electrical inspector and second-guess someone else's work from the safety of your living room or office. It's your turn to identify the violation.

Hint: Disappearing act

Find the Answer

In this photo, we see aPVC pipe secured to a pole. ThePVC pipe itself has not been damaged by sunlight since it is constructed to be "resistantto sunlight effects" in accordance with 352.100. The clip, on the other hand,has beenseverely damagedby the effects of being in the direct rays of the sun for a prolonged period of time. The clip has become very brittle and has cracked almost completely through.

Hint: Disappearing act

This is a violation of 300.6(C), which requiresnonmetallic raceways,elbows, couplings,fittings, supports, and support hardware to be made of material approved for the condition they are placed. These items shall also comply with 300.6(C)(1),which states "where exposed to sunlight, the materials shall be listed as sunlight resistant or shall be identified as sunlight resistant." The material that the clip was made of is clearly not sunlight resistant.