Q. When installing a high-impedance grounded neutral system for a 480V, 3-phase electrical system, the following question arises. Where is the proper location for the grounding impedance (resistor)?
Answer: D
As per 250.36(A), “The grounding impedance shall be installed between the grounding electrode conductor and the system neutral. Where a neutral is not available, the grounding impedance shall be installed between the grounding electrode conductor and the neutral derived from a grounding transformer.”