Q. When are conductors permitted to be terminated based on the 90°C temperature rating and ampacity as given in Table 310.60(C)(67) through Table 310.60(C)(86)?
Answer: C
As noted in 110.40, it is permitted to terminate conductors based on the 90°C temperature rating and ampacity as given in Table 310.60(C)(67) through 310.60(C)(86). This differs from the requirements in 110.14(C)(1), which will not allow this.