Q. What does the NEC require when replacing receptacles in locations that now require arc fault circuit interrupter (AFCI) protection?
A. Effective Jan. 1, 2014, where a receptacle outlet is supplied by a branch circuit that requires arc-fault circuit-interrupter protection [210.12(A)], a replacement receptacle at this outlet must be one of the following [406.4(D)(4)]: