Q. How do I size the conductor and overcurrent protection for an air-conditioner? (Answer based on 2011 NEC.) Find the Answer A. The short circuit and ground fault protective device for a single motor compressor must not be more than 175% of the motor compressor current rating. If the protective device sized at 175% isn’t capable of carrying the starting current of the motor compressor, the next size larger protective device can be used, but in no case can it exceed 225% of the motor ...