Pool Cleanup Ends in Electrocution

Working on a residential pool project, a young laborer loses his life after trying to force a 120V plug into a 240V receptacle while standing in water.

When the construction crew came to work one morning on a residential project, they discovered the tragic scene: an 18-yr-old laborer lying in a puddle of water at one end of an emptied 50-ft-long swimming pool. At this point, no one knew much about the victim, except that he was new to the job and probably didn't have much experience. To help uncover the events leading up to this fatal electrical accident, the insurance company hired our forensic engineering firm to search for answers.

It all started when the new owner of this $2-million house embarked on a rehabilitation project for the house and grounds. When construction reached the final cleanup stage, the pool contractor completed his final washdown on the replastered pool, leaving a 1-ft puddle of water.

Based on interviews with the superintendent and other workers, we began to unravel the unfortunate steps the victim took. Late in the day, the foreman asked him to pick up a sump pump (left in the yard by the pool contractor) and pump out the remaining 1-ft puddle in the pool. Characterized by coworkers as conscientious, the young worker followed these instructions, after everyone left the job site.

The events that followed are inferred, based on the young worker's task at hand. First, he must have picked up an extension cord lying on the patio (the tile c ontractor used this heavy-duty cord to power a tile saw). Next, he plugged it into a 2-pole, 3-wire, grounded 30A, twist-lock type, 240V gang box lying nearby. He'd seen the tile setter use this gang box for his big saw. The worker then pulled this extension cord over the side of the pool and attempted to plug the 2-pole, 3-wire, 120V standard male plug (at the end of the sump pump's 10-ft extension cord) into the receptacle placed at the end of the heavy-duty extension line. At this point, he ran into an obstacle. Since the sump pump's cord had straight blades at the end, it wouldn't fit into the receptacle. This is where he got into trouble.

While standing in the puddle, he attempted to force the 2-pole, 120V male plug into the power cord's 240V female receptacle. Although it's not clear how he got the spades to enter the 240V receptacle, he had pliers in his back pocket. We surmised he bent the blades and put the pliers in his pocket, before attempting to make the connection. At the moment of contact, we assume there was a connection between the plug and receptacle (one or both probably wet), his wet hands, his body, and the puddle. The resulting power flow through his body caused burns on his hands and legs and was enough to cause his muscles to freeze and his heart to stop.

Upon further inspection, we found the power supplied to the site came from a temporary 4 in. by 4 in. power pole, with a 200A fused disconnect switch. This switch fed three other gang boxes strung throughout the site via 4-conductor waterproof cords. The conductors of each cord connected to the disconnect switch with lugs held in place by screws taped into each bus inside the switch. There was no separate fusing of the individual circuits at the switch, nor were there fuses in the gang boxes. Of the 200A fuses at the disconnect switch, one was blown, thus opening the involved circuit.

Since this incident occurred some time ago, prior to the rigorous inspection procedures followed today, such a jerry-rigged electrical arrangement would not meet today's safety standards or accepted practices used by careful electricians. Although we may become irritated at all of the National Electrical Code, OSHA standards, and inspections mandated by current-day construction and building requirements, this case is a good reminder of the importance of such requirements.

This accident clearly resulted from a combination of unfortunate circumstances. First of all, the worker should have received some training regarding the voltages and usage of the available cables and potential dangers of working with electric power in the vicinity of water. Similarly, had someone familiar with the basics of electrical installation and/or pool construction been present, this tragic accident may not have occurred.

This case proves characteristic of many forensic engineering investigations: Accidents are seldom the result of a single action. Rather, they're the combination of unfortunate, simultaneous events. This case ended with the insurance carrier that hired us paying damages on behalf of the general contractor.

Garrett is the chief executive officer for Garrett Engineers, Inc. in Long Beach, Calif.


Want to use this article? Click here for options!





Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Feb 2, 2012 7:54 PM

What's Wrong Here?

Jan 19, 2012 4:06 PM

What's Wrong Here?

Jan 5, 2012 11:53 AM

View all What's Wrong Here?

product spotlight

Labeling tool

Feb 10, 2012 7:58 AM

Labeling tool

The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M TV

Arlington CP9000

Arlington's new 9" diameter ceiling cover plate is the neatest way to cover unused "high hat" cans. With no tools needed, installation couldn't be faster!...

Arlington Gangable Boxes

Designed for new or retrofit applications, these snap-together gangable plastic boxes eliminate the need to construct a multiple-gang steel box out of several individual ones...

Understanding NEC Requirements for Solar Photovoltaic Systems
During this session, Mike Holt will address possible conflicts or confusing NEC requirements, provide tips on proper electrical installation techniques, and discuss the dangers related to improper installations. View this On Demand Webinar!



resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues