What's Wrong Here?
Dec 7, 2005 4:31 PM, By Joe Tedesco
Answer:
Hint: Knot this time — or anytime for that matter
Charles H. Schutz, owner, CHS Electric LLC, Brick, N.J., ran across this cluster of wires while renovating, repairing, and replacing some homeowner electrical work in a house where new owners were moving in. “I was following a wire from a ceiling fan in the bedroom (no box installed), and when I lifted up some insulation I found this,” Schutz said. “I could not resist but to take a picture.”
Splices are to be made in a properly sized junction box. As per 300.15, “A box shall be installed at each outlet and switch point for concealed knob-and-tube wiring.”
The NEC also states, “Fittings and connectors shall be used only with the specific wiring methods for which they are designed and listed.”
Where the wiring method is conduit, tubing, Type AC cable, Type MC cable, Type MI cable, nonmetallic-sheathed cable, or other cables, “a box or conduit body shall be installed at each conductor splice point, outlet point, switch point, junction point, termination point, or pull point, unless otherwise permitted in 300.15(A) through (M).”
Want to use this article? Click here for options!
© 2010 Penton Media, Inc.
Code Challenge
Code Quiz
Mar 11, 2010 12:45 PM, By Steven Owen
When installing outlet boxes for wall-mounted luminaires, when can you use No. 6 screws to secure the luminaire yoke to a plaster ring?...
More Code Quizzes
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
|
Whats Wrong Here?Mar 11, 2010 12:54 PM |
|
What's Wrong Here?Feb 18, 2010 5:04 PM |
|
What's Wrong Here?Feb 4, 2010 5:06 PM |
View all What's Wrong Here?
What's Wrong Here
Sponsored By:

Email