What's Wronge Here?
Dec 8, 2004 12:33 PM, By Joe Tedesco
The short length of unlisted flexible metal conduit that serves this garage door opener was installed without an equipment-grounding conductor.
Per 250.118 of the 2002 NEC, “The equipment grounding conductor run with or enclosing the circuit conductors shall be one or more or a combination of the following:
“(6) Listed flexible metal conduit that is not listed for grounding, meeting all the following conditions:
“a. The conduit is terminated in fittings listed for grounding.
“b. The circuit conductors contained in the conduit are protected by overcurrent devices rated at 20A or less.
“c. The combined length of flexible metal conduit and flexible metallic tubing and liquidtight flexible metal conduit in the same ground return path does not exceed 1.8 meters (6 feet).
“d. The conduit is not installed for flexibility.”
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
Feb 2, 2012 9:02 PM, By Steven Owen
When installing audio distribution cables exposed on the surface of ceilings and sidewalls, the cables shall be supported by which of the following products?
- ...
More Code Quizzes
Code Q&A
Feb 2, 2012 8:58 PM, By Mike Holt
Q. Is it acceptable to use a 14 AWG conductor for the bonding jumper to a receptacle on a 20A branch circuit?
...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
product spotlight
Labeling tool
Feb 10, 2012 7:58 AM
The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.